Modular Switched Mode Rectifier Part number: 010-569-20
|
 |
 |
- 5A output @ 220Vdc
- Power limiting and wide range AC input
- 93% efficiency with power factor correction
- Convection cooled
- Hot swappable, 4RU ultra compact design
Cordex rectifiers bring advanced technology to the DC power industry. Innovative engineering combines the best in efficiency and reliability meeting the power requirements for a variety of system applications. This rectifier is specifically designed to recharge all types of stationary batteries for large utility, petrochemical, and industrial uses.
The Cordex 1.1kW is a compact 4RU allowing five rectifiers and a controller per 19" shelf. In addition to a range of standard features, the convection cooling will maintain ideal operating temperatures in the often dusty environments of utility applications.
Local and remote setup, adjustment, and control is a simple, single-step process with the Cordex CXC System Controller. By utilizing TCP/IP technology, complete configuration and monitoring of power equipment is possible through a network web browser.
|
 |
|
| Electrical |
| Input voltage: |
|
| Nominal: |
208 to 277Vac |
| Operating: |
176 to 320Vac |
| Extended: |
176 to 150Vac (de-rated to 75%) |
| Input frequency: |
45 to 66Hz |
| Power output: |
1100W continuous/module |
| Power factor: |
>0.99 (input current) |
| THD: |
<5% |
| Efficiency: |
>93% |
| Output voltage: |
180 to 320Vdc |
| Output current: |
5A @ 220Vdc (5.5A max) |
| Load regulation: |
Static <±0.5% |
| Line regulation: |
Static <±0.1% |
| Transient response: |
±2% for 50 to 100% load step, 10ms recovery time |
| Wide band noise: |
<30mVrms <150mVp-p |
| Insulation: |
2.5kVac input-earth 3kVac input-output 2kVac output-earth 0.5kVac signals-earth |
| Mechanical |
| Dimensions: |
mm: 177H x 71W x 250D inches: 6.9H x 2.8W x 9.8D |
| Weight: |
2.9kg (6.4lb) |
| Environmental |
| Temperature: |
|
| Operation: |
-40 to 50C (-40 to 122F) (up to 70C/158F power de-rated) |
| Storage: |
-50 to 85C (-58 to 185F) |
| Humidity: |
0 to 95% RH non-condensing |
| Elevation: |
-500 to 4000m (-1640 to 13120ft) |
| Heat dissipation: |
<282BTU per hour (max) |
|
|
|