Top and Front Terminal Batteries |  |  | - Runtimes up to 160 minutes in cable, traffi c and other outdoor UPS applications
- Absorbent Glass Mat (AGM) technology for effi cient gas recombination
- Maintenance-free threaded inserts
- UL-Recognized component
The AlphaCell Batteries provide the ultimate warranties, the longest runtimes and the best longevity in today's demanding outdoor non-temperature controlled environments. AlphaCell AGM batteries are an economical option for broadband, traffi c and other indoor/outdoor UPS applications. With a fl ame-arresting, one-way pressure-relief vent for safety and long life, and a thermally welded case-to-cover bond to ensure a leak-proof seal, Alpha's AGM batteries are classifi ed as non-hazardous material and are not restricted for air, water or surface transport.
Due to the implementation of the HST and the elimination of the provincial sales tax in British Columbia, Canada, the $5 battery levy will be eliminated effective July 1, 2010. The BC Government will continue to fund the programs to offset the revenue loss and will review the Sustainable Environment Fund (SEF) budget annually. | | |
| | General Specifications |
|---|
| Model: | 160 AGM |
|---|
| Warranty: | 1 year full replacement |
|---|
| Service Life: | Average |
|---|
| Runtime (minutes): | 160 |
|---|
| Sealed VRLA: | Valve regulated lead acid |
|---|
| Heat Resistant: | Moderate |
|---|
| Hydrogen Emission: | Low |
|---|
| Terminals: | Threaded insert 1/4" - 20 UNC |
|---|
| |
|---|
| Specifications |
|---|
| Model: | 160 AGM |
|---|
| Typical Runtime (minutes): | 160 |
|---|
| Cells Per Unit: | 6 |
|---|
| Voltage Per Unit: | 12.8 |
|---|
| Conductance Value: | 1300 |
|---|
| Max. Discharge Current (A): | 800 |
|---|
| Short Circuit Current (A): | 3300 |
|---|
| 10 Second Volts @ 100A: | 11.6 |
|---|
| Ohms Impedance 60Hz: | 0.004 |
|---|
| Capacity at 20hrs: (to 1.75VPC) | 88Ah |
|---|
| BCI Group size: | 27 |
|---|
| Weight (lb/kg): | 62/28 |
|---|
| Height w/ terminals (in/mm): | 9.05/229.8 |
|---|
| Width (in/mm): | 12.57/317.8 |
|---|
| Depth (in/mm): | 6.83/173.4 |
|---|
| |
|---|
| Operating Temperature Range |
|---|
| Discharge: | -40 to 71°C (-40 to 160°F) |
|---|
| Charge (with temp compensation): | -23 to 60°C (-9.4 to 140°F) |
|---|
| Float Charging Voltage (Vdc): | 13.5 to 13.8 |
|---|
| AC Ripple Charger: | 0.5% RMS or 1.5% of fl oat charge voltage recommended for best results. Max. allowed = 4% P-P |
|---|
| |
|