Indoor Enclosure |  |  | - Metal enclosure to protect uninterruptible power supply (UPS) from harsh indoor environments
- Castor wheels and screw pads make for easy relocation or securing the enclosure in place, even in high vibration areas
- Glass window to easily view alarm indicators from a distance
- Modern industrial design suitable for many applications
- Optional matching battery enclosure is available allowing for increased extended run-time capability
The Alpha Indoor Enclosure 9 provides a protected, extended run-time UPS solution based on the Alpha FXM power module platform. This enclosure meets the demands of rugged indoor environments where high temperatures and poor air quality exist - particularly where run-times in excess of an hour are required. Examples of applications where the system can be use include Industrial markets (e.g. backing up stand-alone CNC milling machines) and small, mission-critical IT facilities. The enclosure is equipped with a black metal, filtered and gasketed door that provides filtered airflow which protects the UPS and batteries from dust and dirt. Power distribution can be configured for most standard connections and an additional external fan is available for increased airflow in high temperature environments. A matching battery cabinet can be located adjacent to the main enclosure providing room for two additional strings of batteries and room for customer furnished equipment. The unit is designed with easy installation and maintenance in mind.
| | |
| | Environmental Specifications |
|---|
| Operating temperature: | 35ºC at full power with no cabinet fan 45ºC at full power with optional cabinet fan 55ºC at derated power with no cabinet fan 70ºC at derated power with optional cabinet fan | | Storage temperature: | -40º to 75ºC (-40º to 168ºF) |
|---|
| Operating altitude: | 3658m/12,000ft |
|---|
| Operating humidity: | Up to 95% |
|---|
| Power Module | FXM 650 | FXM 1100 | FXM 2000 |
|---|
| | North America | International | North America | International | North America | International |
|---|
| Nominal voltage: | 120VAC | 230VAC | 120VAC | 230VAC | 120VAC | 230VAC |
|---|
| Nominal frequency: | 60Hz | 50Hz | 60Hz | 50Hz | 60Hz | 50Hz |
|---|
| Input current: | 8.0A/10.5A | 4.5A | 16.0A | 8.0A | 20.0A | 12.0A |
|---|
| Output current: | 5.4A | 2.8A | 9.1A | 4.78A | 16.6A | 8.69A |
|---|
| Output power at 50ºC: | 650W/VA | 650 W/VA | 1100W/VA | 1100W/VA | 2000W/VA | 2000W/VA |
|---|
| Output power at 74ºC: | 500W/VA | 500W/VA | 850W/VA | 850W/VA | 1500W/VA | 1500W/VA |
|---|
| Battery String Voltage: | 24/48VDC | 24VDC | 48VDC | 48VDC | 48VDC | 48VDC |
|---|
| |
|---|
| General Specifications |
|---|
| Input voltage range: |
|---|
| 120VAC: | 85 to 175VAC (to 150VAC for FXM 2000) | | 230VAC: | 150 to 328VAC (to 281VAC for FXM 2000) | | Output voltage range |
|---|
| North America: | 108 to 132VAC |
|---|
| International: | 207 to 253VAC |
|---|
| Voltage waveform: | Sine wave |
|---|
| Typical efficiency: | (full resistive load): >98% |
|---|
| Typical transfer time: | <5ms |
|---|
| Audible noise @ 1m: | <40dBA±3V without going to batteries |
|---|
| |
|---|
| Mechanical Specifications |
|---|
| Unit weight: | 70.3kg (155 lbs) estimated + batteries ( w/FXM 650) | 72.6kg (160 lbs) estimated + batteries (w/ FXM 1100) | 74.8kg (165 lbs) estimated + batteries (w/ FXM 2000) |
|---|
| |
|---|
| Agency Compliance |
|---|
| CSA 22.2 No 107.3-03, CE | | EMC: same as FXM | | |
|---|
| Standard Features |
|---|
| Available with FXM 650, FXM 1100, or FXM 2000, Cabinet can house four AlphaCell 180/210 GXL batteries, or eight AlphaCell | | 195GXL-FT batteries, Casters with brake, Washable/replaceable air filter, Power input: 8' line cord w/ NEMA plug, IEC connectors, or terminal blocks, Power output: NEMA receptacles, IEC connectors, or terminal blocks, Includes floor brackets for permanent fixing, Display window for quick status checking | | |
|---|
| Options |
|---|
| Alpha Universal Automatic Transfer Switch, Alpha Universal Generator Transfer Switch, Surge Suppressor, AlphaGuard™, External Cabinet Fan, Extended Battery Cabinet for additional runtime, a variety of input and output connections are available | | |
|---|
| Battery Runtimes (hours) |
|---|
| Four x 195 GXL | w/ FXM 650: | w/ FXM 1100: | w/ FXM 2000: |
|---|
| 4.8 hours | 2.6 hours | 1.2 hours | | Eight x 195 GXL | w/ FXM 650: | w/ FXM 1100: | w/ FXM 2000: |
|---|
| 10.5 hours | 5.8 hours | 2.9 hours |
| |
|