220V High Voltage Integrated Systems Part Number: 030-789-20 |  |  | - 15A system capacity @ 220V
- Cordex 1.1kW modular rectifiers
- Wide range AC input
- Front accessible for rack or wall mounting
- Ethernet and SNMP communications
- Designed for industrial and utility applications
The Cordex 3.3kW high voltage integrated power system provides the best in efficiency and reliability meeting the power requirements for a variety of system applications. This system is specifically designed to recharge all types of stationary batteries for large utility, petrochemical and industrial uses.
The Cordex 3.3kW is a compact 7RU integrated system, with up to three Cordex 1.1kW rectifiers in a 19in shelf available for rack or wall mounting. Local and remote setup, adjustment and control is a simple single-step process via the Cordex CXC touch screen system controller or via ethernet on standard Windows Internet Explorer. Battery management and data logging are standard system features. |  |
| | Electrical | | Input voltage: | | | Nominal: | 208 to 277VAC | | Operating: | 176 to 320VAC | | Extended: | 176 to 150VAC (de-rated to 75%) | | Phase: | 1 or 3 | | Frequency: | 45 to 66Hz | | Power factor: | >0.99 | | Efficiency: | >93% (50 to 100% load) | | Output voltage: | 90 to 160VDC | | Current: | 8.8A per module @ 125VDC, 5A per module @ 220VDC, up to 3 modules per shelf | | Load regulation: | Static <±0.5% | | Line regulation: | Static <±0.1% | | Transient response: | ±2% for 50 to 100% load step, 10ms recovery time | | Wide band noise: | <10mVrms <80mVp-p | | Insulation: | 2.5kVAC input-earth 3kVAC input-output 2kVAC output-earth 0.5kVAC signals-earth | | Mechanical | | Charger enclosure: | Wall or rack mount | | Dimensions: | mm: 12.2H x 17.1W x 11.9D inches: 309H x 434W x 302D | | Weight: | 12.59kg (27.76lb)* | | Enclosure: | NEMA 1 (charcoal finish) | | Environmental | | Temperature: | | | Operation: | -40 to 50C (-40 to 122F) | | Extended: | Rectifier de-rated to 600W @ 65C (149F) | | Humidity: | 0 to 95% RH non-condensing | | Cooling: | Natural convection | | Heat dissipation: | <900BTU per hour/system |
| |
|