Standard 48VDC Power System Part Number: 053-990-20 |  |  | - 48VDC systems using high density 1.8kW rectifiers
- Front access DC connections
- Integrated CXCI advanced digital controller
- Wide range AC input
- Optional integrated systems with battery trays
- Integrated system shunt and LVD
Alpha CXPS standard power systems bring proven Cordex technology into a standard integrated system package. The CXPS 48-1.8-i uses high density 48V-1.8kW rectifiers, a front access distribution center, and the advanced, slim CXCi controller.
The CXPS 48-1.8-i is a perfect solution for various small 48VDC applications, and with a small footprint and high temperature operation, is ideal for outside plant installations. The system provides up to 150 Amps of 48VDC power, and includes 14 load and 4 battery breaker positions along with a low voltage battery disconnect and shunt.
The system is a universal 19" or 23" rack mount design and can be easily integrated into various racks, boxbays, or enclosures. The system can also be ordered factory-installed into various Alpha rack configurations including systems with pre-wired battery trays. |  |
| | Electrical | | Input: | | | Voltage: | 176 to 312VAC (nominal) 90 to 176VAC (de-rated O/P power) | | Current: | 14.6A @ 240VAC (per module) 12.2A @ 120VAC (per module) | | Frequency: | 45 to 66Hz | | Efficiency: | >91% (50-100% load @ nominal voltage) | | Power factor: | >.99 | | Output: | | | Current: | | | System: | 150A max @ nominal I/P 96A max @ 120VAC I/P | | Rectifier: | 37.5A @ 48VDC (nominal I/P) 24A @ 48VDC (115 to 135VAC) (de-rated linearly to 18.75A @ 90VAC) | | Power: | | | System: | 7200W max @ nominal I/P 4600W @ 120VAC I/P | | Rectifier: | 1800W max @ nominal I/P 1150W (115 to 135VAC) (de-rated linearly to 900W @ 90VAC) | | Mechanical | | Dimensions: | mm: 222H x 438W x 310D inches: 8.75H x 17.24W x 12.2D (-000 configuration - excludes mounting brackets, rear cover, and module handle) | | Weight: | System: 19kg (42lb) Rectifier: 2.8kg (6.2lb) each | | Mounting: | 19/23" universal mount (center or flush) | | Connnections: | | | Load breaker: | Hot: ¼in-20 studs on ⅝in centers Return: ¼in holes on ⅝in centers | | Battery breaker: | 4x sets, ¼in-20 studs on ⅝in centers | | Return bar: | 18x sets, ¼in holes on ⅝in centers | | AC input: | Box type terminal block, 6 to 16mm2 (10 to 6AWG) | | Alarm: | Screw terminal 1.31mm2 to 0.128mm2 (#16 to #26 AWG) | | CXCI input: | 25-pin D-Sub cable | | Access: | Front access after installation | | Environmental | | Temperature: | -40 to +65C (-40 to 149F) -40 to +75C (-40 to 167F) de-rated output | | Humidity: | 0 to 95% RH non-condensing | | Elevation: | -500 to +2800m (-1640 to 9186ft) -500 to +4000m (-1640 to 13124ft) with de-rated output |
| |
|